Analytic 25A, 48 V, 110 V AC, 60 Hz, 2 Bank, AC Battery Charger BCA1505-110-48
BCA1505 AC Battery Charger
NSN#
BCA1505
BENEFITS
- Ultra-Quiet
- Power sensitive electronics without interference
- Rugged & Reliable
- Ensure years of safe and trouble free operation
- Fast & Accurate Charging
The BCA1505 battery charger provides up to 1350 watts to charge a 12 24, 36,
48 or 72 Volt battery system (2 bank) from a 110 or 220VAC source. The batteries
must share a common ground.
This all-new single board design incorporates state of the art switchmode
technology for unmatched efficiency and ultra-quiet operation. Multiple stages
of filtering reduce radiated or conducted noise to very low levels. Extra
features include visual indicators for low input voltage, charging and
over-temperature.
Safety features include both charger and battery over-temperature shutdown,
current limiting, short circuit protection with automatic recovery, input
undervoltage shutdown and output over-voltage crowbar.
Optional features include a 3-Bank Load Splitter. We are confident that you
will get many years of reliable service from this AC Battery Charger.
Features
- Military-Grade extrusion ensures a high tolerance for shock and vibration
- Ultra-quiet low EMI operation
- Can be left permanently connected
- Can function as a power supply
- Dry contact output fail relay
- User selectable 2 or 3 stage charging profile
- Temperature compensated charging
- Over-temperature shutdown
- 3 Bank Load Splitter Available
- Audible & visual indicators for output overload, low input voltage, low
output voltage & over-temperature
- Short circuit protection
- Output over-voltage crowbar
- Inrush Current Limiting with solid state bypass
- 110/220 Vac auto-ranging input option
- Thermostatically controlled fan
- 3 year parts and labour warranty
Applications
- Commercial Marine
- Military and DHS
- Electric Utilities and Substations
- Ideal as a Trade Show Power Supply for Auto Shows
- OEM Applications
- Field Work / Construction Sites
- Solar Power Systems
- Emergency Power Backup (UPS)
- Security Systems
- Charge any 12, 24, 32, 48 or 72 Volt (as well as custom voltage from
12-72VDC) Battery System
Electrical [Input]
Nominal Vac (ip)
|
110
|
220
|
Actual (Vac)
|
105-125
|
210-250
|
Input Amps (Max)
|
16.2
|
8.1
|
Input Breaker
|
25A
|
Input Frequency
|
45-65 Hz
|
Noise on Input
|
< 50mV
|
Electrical [Output]
Output Nominal (op)
|
12
|
24
|
32
|
48
|
72
|
Output Volts (DC)
|
13.6
|
27.2
|
36.3
|
54.4
|
81.6
|
Absorption Voltage (VDC)
|
13.6
|
28.8
|
38.4
|
57.6
|
86.4
|
Charging Amps
|
75
|
50
|
37
|
25
|
16
|
Absorption to Float
|
15A
|
7.5A
|
5.6A
|
3.8A
|
2.4A
|
Battery Banks
|
2(3 Bank Load Splitter Available)
|
Battery Size
(Amp Hrs.)
|
400-600
|
200-300
|
150-230
|
100-150
|
70-100
|
Output Crowbar
|
17.0 0.5V
|
34.0 1.0V
|
45.4 1.3V
|
68 2.0V
|
102 3.0V
|
Equalize Voltage (VDC)
|
15.5
|
31
|
41.3
|
62
|
93
|
Temperature Compensation Coefficient
|
-15mV/C
|
-30mV/C
|
-40mV/C
|
-60mV/C
|
-90mV/C
|
Output Ripple & Noise
|
< 50 mV
|
Duty Cycle
|
Continuous 100% for 24 hours per day
|
Efficiency
|
> 80% @ Maximum Output
|
Stages
|
2 or 3 selectable
|
Regulation
|
< +/- 0.5%
|
Environmental Specification
Operating Temp. Range
|
-25 to +40C @ maximum output
Derate Linearly 2.5% per C from 40C
(Optional -40C to +55C extra wide temp. operation avail.)
|
Humidity
|
0 - 95% Relative Humidity
(non-condensing) with optional conformal coating
|
Audible Noise
|
NONE db @ 3 ft (34.5 dB when fan operating
|
Typical Service Life
|
>10 years (87,600 hours)
|
Isolation
|
Input-Case & input-output 1500VDC
Output - Case 500VDC
|
Vibration
|
Meets Loose Cargo Test
|
Mechanical Specification
Length
|
16.16 in/ 41.14 cm
|
Width
|
8.35 in/ 21.21 cm
|
Height
|
4 in/ 10 cm
(withour carrying handle)
|
Clearance
|
1 inch (2.5 cm) all around
|
Material
|
Marine Grade Aluminium
|
Finish
|
Black
|
Fastenings
|
All 18-8 Stainless Steel
|
Weight
|
14.4 lb / 6.6 kg
|
Connections
|
Flying Leads
|
Warranty
|
3 years
|
Safety
|
Designed to meet CSA 22.2.107.1 & UL458
|
|