Analytic 10A, 24V Out, 230-280V In, Isolated DC/DC Battery Charger, 3 Bank, BCD310-250-24
BCD310 DC Battery Charger
NSN#
BCD310
BENEFITS
- Ultra-Quiet
- Power sensitive electronics without interference
- Rugged & Reliable
- Ensure years of safe and trouble free operation
- Fast & Accurate Charging
The BCD310 battery charger provides up to 300 watts to charge a 12 or 24 or
48 Volt battery system from a 110V, 220V or 300VDC source. The batteries must
share a common ground but the source can be on a different positive or negative
ground.
Multiple stages of filtering reduce radiated or conducted noise to very low
levels. Extra features include adjustable output voltage, audible and visual
indicators for low input voltage, 3-Bank charging, low output voltage, over
temperature and an equalize charging cycle. Safety features include reverse
input protection, over-temperature shutdown, current limiting, short circuit
protection with automatic recovery, input undervoltage shutdown, reverse battery
protection, output overvoltage crowbar and a dry contact alarm relay output.
Optional features include a Digital Volt/Ammeter, a Remote Control Panel,
and/or a second Battery Temperature Sensor. We are confident that you will get
many years of reliable service from this DC Battery Charger.
Features
- Fully Isolated Design
- Adjustable output voltage for charging standard or deep cycle lead-acid,
VRLA or Gel cell type battery
- Transient Voltage Suppressor
- Extremely rugged and well suited for marine and other demanding
environments
- High tolerance for shock and vibration
- Ultra-quiet low EMI operation
- Can be left permanently connected
- Spark free connection
- User selectable 2 or 3 stage charging profile
- Audible & visual indicators for output overload, low input voltage, low
output voltage & over-temperature
- Over-temperature shutdown
- Short circuit protection
- Output over-voltage crowbar
- Inrush Current Limiting with solid state bypass
- Dry contact output fail relay
- 3 year parts and labour warranty
Applications
- Marine & other Rugged Environments
- Electric Utilities and Substations
- Manufacturing Plants
- Steel Mills
- Military Applications (COTS)
- Industrial Controls
- OEM Applications
- Solar / Alternative Power Systems
- Fuel Cells
- Charge any DC/DC System
Electrical [Input]
Nominal (ip) |
110 |
250 |
300 |
Actual (Vdc) |
100-140 |
230-280 |
280-360 |
Input Amps (Max) |
3.8 |
1.7 |
1.4 |
Input Fuse (MDA) |
5 |
3 |
2 |
Noise on Input |
< 25 mV |
Electrical [Output]
Output Nominal (op) |
12 |
24 |
48 |
Output Volts (DC) |
13.6 ? 0.05 |
27.2 ? 0.05 |
54.4 ? 0.05 |
Absorption Voltage (Vdc) |
14.4 |
28.8 |
57.6 |
Charging Amps |
20 |
10 |
5 |
Absorption to Float |
3.0 Amps |
1.5 Amps |
0.75 Amps |
Output Adjustment (Vdc) |
? 1.0 V |
Output Fuses (AGC) |
25A |
15A |
10A |
Battery Banks |
1, 2 (3 bank option available) |
Battery Size (Amp Hours) |
80-120 |
40-60 |
20-30 |
Output Crowbar |
16.0 ? 0.5V |
32.0 ? 1.0V |
63.9 ? 2.0V |
Output Ripple & Noise |
< 25 mV |
Regulation
(Line & Load) |
< +/- 0.5% |
Temperature Comp. |
-30 mV/?C |
-60 mV/?C |
-120 mV/?C |
Duty Cycle |
Continuous 100% for 24 hours per day |
Efficiency |
> 75% @ Maximum Output |
Stages |
2 or 3 (user selectable) |
Environmental Specification
Operating Temp. Range |
-25? to +40?C @ maximum output
Derate Linearly 2.5% per?C from 40?C
(Optional -40?C extra wide temp. operation avail.) |
Humidity |
0 - 95% Relative Humidity
(non-condensing) with optional conformal coating |
Audible Noise |
NONE - ?db @ 3 ft |
Typical Service Life |
>10 years (87,600 hours) |
Isolation |
Input-Case & Input-Output 1500VDC
Output-Case 500VDC (1500VDC @ 48V O/P) |
Mechanical Specification
Length |
9.6 in / 24.4 cm |
Width |
8.2 in / 20.8 cm |
Height |
3.5 in / 6.4 cm |
Clearance |
1 inch (2.5 cm) all around |
Material |
Marine Grade Aluminium |
Finish |
Black Anodize / Powder Epoxy Coat |
Fastenings |
All 18-8 Stainless Steel |
Weight |
7.5 lb / 3.4 kg |
Connections |
Four contact output terminals |
Warranty |
3 years |
Safety |
Designed to meet CSA 22.2.107.1 & UL458 |

|