Analytic Pure Sine Wave Inverter 300VA, (24, 32, 48, or 125VDC Input), 110/220VAC Output, 50/60Hz, IVS300
The IVS300 Series is a highly compact DC/AC inverter that uses established
design techniques to ensure high reliability.
Suitable for a wide range of applications, the IVS300 features full
electronic protection, high efficiency and low output noise. The built-in fan
provides sufficient airflow for operation without de-rating up to 50°C ambient
temperature. Extended operating temperature (-40 to +65°C) is available.
The inverter can be loaded with a fluorescent lamp load up to the
full-specified output power.
Benefits
- Ultra-Quiet
- Power sensitive electronics without interference
- Rugged & Reliable
- Ensure years of safe and trouble free operation
Features
- Input is filtered to EN 55022 Class B
- Very low 60Hz input ripple current
- Compact size
- Modular design, light weight
- Multiple input and output voltages available
- 300VA of output power
- Full electronic protection
- Field-proven design topology
Applications
- Marine / Automotive / RV
- Electric Utilities and Substations
- Telecom Power Plants
- Manufacturing Locations
- Steel Mills
- Military Applications (COTS)
- Industrial Controls
- OEM Applications
- Solar / Alternative Power Systems
- Fuel Cells
Electrical [Input/Output]/ Mechanical Specification
Input Voltage |
24V, 36V, 48V, 125VDC +/-15% are standard
Other inputs available, please consult factory |
Input Protection |
Thermal fuse, Inrush current limiting, Reverse polarity protection |
Isolation |
Input to chassis 500VDC for < 60V input / 1500 VDC for > 60V input
Input to output 2250VDC / Output to chassis 2250VDC |
Output Voltage |
115VAC / 60Hz or 400Hz @ 2.6A continuous OR 230VAC / 50 Hz @ 1.3A
Continuous with grounded neutral
Isolated floating output optional (Consult factory for other voltages and
frequencies) |
Wave Form |
Sinusoidal |
Total Harmonic Distortion |
Less than 5% at full load |
Efficiency |
Min. 80% at full load |
Line Regulation |
Max. ± 0.5% |
Load Regulation |
Max. ± 6% from 10% load to full load (± 1% option available) |
Output Protection |
Current limiting with short circuit protection; Thermal shutdown with
automatic recovery in case of continuous overload or insufficient airflow |
EMI |
Meets EN 55022 Class A as a minimum |
Load Crest Factor |
Maximum 3.0 at 90% load |
Operating Temperature Range |
0 °C to +50°C. Extended temperature ranges available |
Humidity |
5 - 95% non-condensing |
Temperature Drift |
0.05% per °C over operating temperature range |
Dimensions |
6.0” x 2.63” x 13.82” enclosed case (H x W x L) |
Connections |
Input: Compression-type terminal / Output: Standard AC receptacle |
Weight |
4.6 lb (2.1 kg) |
Safety |
Compliance to C22.2 No. 107.1 - 01 and UL 458 |
Warranty: 24 months subject to application within good
engineering practice
Enhancements to these general specifications can be accommodated upon
request
Designed to meet common approval requirements. Specifications Subject to
Change without Notice
Designed and Manufactured in Canada |
|